HC900 Control System Architectures - Scope of SIL Certification for HC900 Control System Architectures 
16    HC900 Process & Safety Controller Safety Manual  Revision 1.9 
    01/14 
Scope of SIL Certification for HC900 Control System Architectures 
The HC900 control systems shown in all of the topologies above are included in this SIL certification with 
the exception of: 
•  900 Control Station and other supervisory control systems – These systems are outside the scope of 
SIL certification for the HC900 Control System.  However, the non-interference of these 
communication protocols is part of the scope to allow connection of these interfaces during safety-
related operations. 
•  Hubs switches and cabling – These are part of building the network and are part of the “black 
channel” and are not required for SIL certification. 
•  The PFQ (Pulse Frequency Quadrature) I/O module is non-interfering in this SIL certification 
project. 
•  RTPs (Remote Terminal Panels) and associated cables are not part of this SIL certification project. 
•  Attention: An HC900 control system retains its SIL2 rating only if all of the components that 
comprise the HC900 control system are operating within their operating temperature range.