EasyManuals Logo

Honeywell HCE80 Mounting And Operation Manual

Honeywell HCE80
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
Help with problems
24
Problem Cause/solution
Power LED does not
light up when the
power is switched on.
Mains voltage not connected.
f Check voltage of
electrical outlet.
f Check fuse at underfloor
heating controller.
LEDs 1...8 of the
zones do not
illuminate green
continuously during
commissioning.
The room name cannot
be assigned.
f Check the antenna connection.
f Reassign the zone,
if applicable.
LEDs 1...8 of the
zones do not
illuminate red
continuously during
commissioning.
The room setpoint generator/
sensor cannot be assigned.
f Check whether batteries in
the room setpoint generator/
sensor are inserted properly.
f Check the radio connection.
f Check the antenna connection.
Rooms are not
heated/cooled.
f Check heating and
inlet temperature.
f Check the switch for setting
normally open/normally
closed (see Page 10).
f Check the fuse of the
underfloor heating controller.
If fuse is defective:
f Check the thermal actuators
for a short circuit.
f Change the fuse.
Problem Cause/solution
The LED lights
up red after
commissioning.
There is a fault in one of the
temperature zones (see Page 15).
f Check the radio connection.
f Check the antenna connection.
f Check whether zone is
assigned correctly.
f Check the batteries of
the assigned devices.
The room temperature
is not controlled
correctly.
f Check whether a room
setpoint generator/sensor
is assigned to the room.
The LED
flashes rapidly.
No device installed.
f Install the devices again.
The LED flashes.
No antenna connected
or antenna defective.
f Check the antenna connection.
f If applicable, replace the
antenna by a new one.
The red LED of the
learned zone flashes
after binding.
The evohome controller has
not yet sent a valid sensor value
of the DTS92/T87RF to the
underfloor heating controller.
The red LED extinguishes
after approx. 3 minutes.
Errors and elimination

Table of Contents

Other manuals for Honeywell HCE80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HCE80 and is the answer not in the manual?

Honeywell HCE80 Specifications

General IconGeneral
BrandHoneywell
ModelHCE80
CategoryController
LanguageEnglish

Related product manuals