Basicsforinstallingthedeviceinapipe
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 27
No. Meaning
11 Ventline
12 Reliefline
13 Blowdownline
Followingisthemeaningoftheacronyms:
Acr. Meaning
DN Nominalsizeofpipe
L
uR
Undisturbedlengthofpipe
*Shut‐offdevicewithundisturbedflowpattern(ballvalve)canbeincorporated
4.2 Meterruncharacteristics
Thefollowingrecommendationsarebasedonthemeasuringlineconnectionconditionsset
forthinstandards(DIN) EN 334and(DIN) EN 14382.Thecompanyoperatingthesystemis
thesolepartyresponsibleforthemeterrunworkingproperly.
Apipeareawithasteadyflowpatternmustbeselectedforthesensingpoint.There
mustnotbeanycomponentsthatdisturbtheflowdirectlyupstreamanddownstream
ofthesensingpoint,e.g.,orificeplates,expanders,bends,junctions,shut‐offdevices,
etc.
Theflowrateatthesensingpointshouldnotexceedapprox. 25 m/s,dependingonthe
systemconditions.
Inthecaseofspecificsystemcircuits(suchas gasregulatinglinesforgasengines)andin
thecaseofgasburners,flowrateshigherthan25 m/smaybeallowedfollowingcon‐
sultationwiththemanufacturer.
Withinalow‐pressurerangeofuptoapprox. 250 mbar,amaximumflowrate
of approx. 15 to 20 m/sisrecommendedatthesensingpoint.Onacase‐by‐casebasis,
andfollowingconsultationwiththemanufacturer,evenlowerflowratesmaybeal‐
lowed.
Standardsusedasabasis
Conditionsforthemeter
run