Malfunctions
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 42
7 Malfunctions
Topic Page
Malfunctions 42
7.1 Malfunctions
Ifnothandledproperly,pressurizedpartscanmoveandcauseseriousinjuries.Ifnot
handledproperlyorintheeventofadefect,gascanescapefrompressurizedcomponents
underhighpressureandcauseseriousinjuriesandevendeath.Beforeyoustartworking
onthesecomponents:
Closeallconnectionsleadingtothegas‐carryingline.
Establishadepressurizedstatus.Residualamountsofenergymustbedepressurizedas
well.
AlwayscontactthemanufacturersAfter‐SalesServiceDepartmentfortroubleshootingifone
ofthefollowingoccurs:
Youarenotabsolutelysurewhattheexactfaultis.
Thefaultthatoccurredisnotdescribedinthetablebelow.
Thepossiblecausebehindthefaultisnotlistedinthetablebelow.
Despiteyourtroubleshootingattempts,thefaultpersists.
Malfunctionsandabnormalities
Thefollowingtablecontainsadescriptionofmalfunctionsandabnormalitiesthatmayoccurduringtheoperationandlists
procedurestocorrectthem:
Malfunction Possiblecauses Correction
Outletpressuretoohigh
Thesettingfortheactiveregulatorspilotistoo
high.
Unscrewthepilot’spilotspringabituntilthe
desiredpressureisreached.
Theactiveregulatorhasfailedandthemonitor
regulatorisoperating.
Determinewhattheproblemwiththeactive
regulatoris.
Onlyincaseofaverylowambient/operating
temperature:Thepilotheaterhasfailed.
Restoretheheatingfunction.
Outletpressuretoolow
Thesettingfortheactiveregulatorspilotistoo
low.
Screwinthepilotspilotspringabituntilthe
desiredpressureisreached.
Thepressuredifferencebetweentheinletand
outletistoosmall.
Increasetheupstreampressureifpossible.
Thevalveisopenalltheway.Thesystemis
unabletodeliverenoughpressure.
Heavysoilinginthereliefchamber.
Thereisnoupstreampressure.
Checkwhetherthesafetyshut‐offvalveorthe
monitorregulatorhasclosed,aswellasthe
reasonforthis.
Theloadingpressureistoolow. Checkthefilterinsertforsoiling.
Onlyincaseofaverylowambient/operating
temperature:Thepilotheaterhasfailed.
Restoretheheatingfunction.
Themonitorregulatorisactiveduring
normaloperation.
Thechosenpressuredifferencebetweenthe
monitorregulatorandtheactiveregulatoris
toosmall.
Eitherscrewinthemonitorpilotssetscrewa
bitmoreorunscrewtheregulatorpilotsset
screwabit.
Thesafetyvalverespondsbeforethe
monitorregulatorintervenes.
Themonitorpilot’ssetpointistoohighoristoo
closetothesafetyvalve’ssetpoint.
Lowerthemonitorpilot’ssetpointorraisethe
safetyvalve’ssetpoint.