Verify that the green led “Power present” is lighted.
Verify that all the other led are off.
Perform the procedure “lamp test” and verify that the display and all the bright indications light up for a few
seconds.
Remove the 230 Vca network supply from the AM1000 control panel and verify the following conditions:
• the indication on the display “Mains Trouble”.
• Yellow Led “FAULTS” flashing
• Yellow led “POWER” on
• General trouble relay on.
• Verify the battery tension, if the sum of the two tension is lower than 20.5 V it is necessary to substitute
them.
Connect the 230 Vca network supply to the control panel, push the “ACK” key and verify the following
conditions:
• The indication “Mains Trouble” is not displayed.
• Yellow led “FAULTS” off.
• Yellow led “POWER” off
• General trouble relay off
Alarm a device on the line 1 and verify:
• Red led “ALARM” flashing
• Siren output on
• Alarm visualized on the display
Push the “Silence BUZZER “ key and afterwards the “Sounder Silence/Restore” key; on the display is
visualized the request to insert the level 2° password.
Type the password and verify:
• Visualization on the display, on the op right, of the icon concerning the output silenced siren
• Red led “ALARM” on.
• Siren output off.
Pushing the “RESET ” key on the display is visualized the request to insert the level 2° password.
Type the password and verify the following conditions:
• Red led “ALARM” off
• Siren output off.
• Any alarm signalization present on the display
At the end of the maintenance leave the control panel in stand-by (without alarm or trouble indications) and
verify that the led “Power present “ is on.