34 BACNET-GW-3 Installation and Operation Manual – P/N LS10014-000NF-E:C6 5/5/2017
B.6 Standard Object Types Supported - Multi-State Input
Standard Object Types
Present Value
BACnet
Enumeration
NFN State
1 None Normal
2 None All statuses other than those included in 3 and 4 below.
3 None Security Trouble, Fire Trouble, Non-Fire Trouble
4 None Fire Device or Zone Disabled, Non-Fire Device
Disabled
Event State
BACnet
Enumeration
BACnet Event State NFN State
0 EsNormal Normal
1 EsFault Security Trouble, Fire Trouble, Non-Fire Trouble, Fire
Device Disabled, Non-Fire Device Disabled
2 EsOffNormal All statuses other than normal and fault.
Reliability
BACnet
Enumeration
BACnet Reliability NFN State
0 reNoFaultDetected All statuses other than trouble.
7 re_UnreliableOther Security Trouble, Fire Trouble, Non-Fire Trouble
Status Flags
Boolean
BACnet Status
Flags
NFN State
0,0,0,0 Normal
1,0,0,0 InAlarm Fire Alarm, Security Alarm (Life/Property), Critical
Process Alarm (Life/Property), Medical Emergency
1,1,0,0 InAlarm, Fault Security Trouble, Fire Trouble, Non-Fire Trouble,
PreAlarm
1,0,0,1 InAlarm,
OutOfService
Fire Device or Zone Disabled, Non-Fire Device
Disabled
Out of Service
Boolean NFN State
0 FALSE All statuses other than disable
1 TRUE Fire Device or Zone Disabled, Non-Fire Device
Disabled