ID3000/ID2000 Fire Panel Configuration Tool Manual
Loop Devices
3 - 11 997-291, Version 3.05
November 2010
Co-operative Multi-sensing
Co-operative sensing is carried out
automatically between sensors in the same
zone with consecutive addresses and in the
same cell, or no cell. An example of VIEW™
sensor co-operative grouping is given
opposite.
VIEW™ Sensor Sensitivity
Most local codes of practice require that very
low levels of alarm sensitivity selection be
tested on-site before implemention. Alarm
sensitivity level 6 (L6) and below generally
require a 90-day test to ensure the sensor
environment is suitable for a higher sensitivity
setting. This is not required for high levels of
pre-alarm sensitivity selection.
Calibration
Each VIEW™ sensor has to be calibrated on
first operation with the panel. The procedure
is given in the Panel Configuration manual.
Co-operative Multi-sensing: example
Loop Address Type Zone Cell
2 10 VIEW 3 -
2 11 VIEW 3 -
2 12 VIEW 3 -
2 13 VIEW 3 84
2 14 VIEW 3 84
2 15 VIEW 3 84
2 16 VIEW 3 88
2 17 VIEW 3 88
2 18 VIEW 3 88
2 19 VIEW 3 110
2 20 VIEW 3 110
group
group
group
group