INSPIRE E10/E15 Control Panels - Operating instructions
FIRE CONDITION
When one or more fire events occur, the screen turns red, the
first zone in alarm and the time the zone went into the fire
condition is displayed . A flashing indication is given of the
first Zone in Fire . Also, the total number of active zones in
fire is shown . For fire events, the information on the display
is supported by lit general FIRE LED .
The panel buzzer provides an audible sound and the MUTE
BUZZER key is lit to prompt an action.
WHAT DO I NEED TO DO?
Use the information provided by the Display and the LEDs to
understand quickly the situation and what action needs to
be taken. To assist this process, the panel’s display indicates
the zone location(s) of the fire event(s). Use the information
provided to identify the geographic source of the fire. Follow
site procedures on what to do in the event of a fire.
01 To silence panel buzzer select MUTE BUZZER on the
Touch Screen or press the push button on the panel.
02 Log in with your Access level 2 password.
03 If configured, the Alarms delay will be activated
and will be replaced by the Verification Delay if the
Verification delay button is pressed. Note the DELAY
ACTIVE LED will be lit and the count-down time will now
show the Verification delay. The Delay can be forced to
end by selecting the End Delay button.
04 With the emergency over and when it is safe to do so
select SILENCERESOUND button to
silence Alarms .
05 When the devices responsible for the
alarm is cleared for normal operation
then select RESET touch screen or
push button on the panel.
Accident and Emergency Ground Floor - West
DELAY ACTIVE
FIRE
VdS
SILENCE-RESOUND
MUTE BUZZER RESET
Verication delay