2. Specifications
2.2. Certifications and Approvals
4 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3
March 2012
2.2 Certifications and Approvals
Transmitter
Refer to product lable for applicable ratings.
Table 2-2 Certifications and Approvals
AGENCY TYPE OF PROTECTION Ambient
Temperature
Product Applicability*
Intrinsically Safe:
Class I; Division 1; Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1; T4
Class I, Zone 0 Ex ia IIC T4
Class I, Zone 0 AEx ia IIC T4
-40
o
C to +85
o
C : Battery
-40
o
C to +80
o
C : DC
Supply
Pressure
Temperature/ Discrete
Inputs
Corrosion
High Level INPUT (HLAI)
Universal I/O
Nonincendive:
Class I; Division 2; Groups A, B, C, D;
Class II, Division 2, Groups F, G;
Class III, Division 2, T4
Class I, Zone 2 Ex nA IIC, T4
Class I, Zone 2 AEx nA IIC, T4
-40
o
C to +85
o
C : Battery
-40
o
C to +80
o
C : DC
Supply
Pressure
Temperature/ Discrete
Inputs
High Level INPUT (HLAI)
Universal I/O
Explosion-Proof/ Flameproof:
Class I, Division 1; Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1; T4
Class I, Zone 1 Ex d IIC T4
Class I, Zone 1 AEx d IIC, T4
40
o
C to +85
o
C : Battery
-40
o
C to +80
o
C : DC
Supply
Pressure
Temperature/ Discrete
Inputs
Corrosion
High Level INPUT (HLAI)
Universal I/O
Enclosure: Type 4X/ IP66
CSA
1903673
(USA and
Canada)
Standards Used:
CSA-C22.2 No. 30:M1986
CSA-C22.2 No. 94:M1991
CSA E60079-0: 2002
CSA E60079-15: 2002
FM 3600: 1998
FM 3615: 2006
UL 916:1998
CSA-C22.2 No. 142:M1987
CSA-C22.2 No. 157:M1992
CSA E60079-1: 2002
CSA E61241-0: 2002
FM 3610: 1999
ANSI/ ISA 12.12.02: 2003
CSA-C22.2 No. 213:M1987
CSA-C22.2 No. 60529:2005
CSA E60079-11: 2002
CSA E61241-1: 2002
FM 3611: 2004
UL 50:2003