5. Operation
5.3. Transmitter PV display
22 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3
March 2012
Table 5-5 PV status
PV status Cause - Action
(blank)
PV is normal – no action required
BAD
Possible calibration error – Clear calibration
AITB can not execute due to internal firmware state – Attempt cold restart of
device.
AITB can not execute due to hardware fault – Replace sensor board
Sensor failure – Check Connection between Sensor board and Meter Body.
Meter Body Characterization Data is Bad – Replace Meter Body
Meter Body A/D Failure – Replace Meter Body
Meter Body Sensor Fail – Replace Meter Body
Configuration is bad – Check possible units and range settings for input type
and corr
ect AIT
B configuration.
Hardware fault detected - Replace sensor board
UNC
Warning: Calibration (zero or trim) is causing excessive adjustment to
characteri
zation value.
Warning: Input inaccurate due to uncertain input data integrity.
Warning: Input inaccurate due to input conversion limitations or resolution.
Warning: Input outside of characterized range. Value is estimated.
Table 5-6 Device status
Transmitter
display
OneWireless User
Inteface display
Definition What to do
OUT SVC OOS
All channels are out of
service.
Restore mode to Auto in
OneWireless User Inteface.
SENS ERR Sensor Error
Sensor can not access
meter body A/D
converter.
Check connection between sensor
module and meter body. If still
doesn't work, replace sensor. See
page 38.
CHAR ERR Characterization Error
Sensor can not access
meter body
characterization or the
characterization is
invalid.
Check connection between sensor
module and meter body. If still
doesn't work, replace sensor. See
page 38.
OVR TEMP Over Temperature
The meter body has
exceeded the maximum
temperature as defined
by the meter body
characterization data.
Determine cause excessive
temperature.