5. Operation
5.3. Transmitter PV display
Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual 21
March 2012
Description FLOW
LPH liters per hour
LPD liters per day
MLPD million liters per day
CFPS cubic feet per second
CFPM cubic feet per minute
CFPH cubic feet per hour
CFPD cubic feet per day
SCFPM standard cubic meters per second
SCFPH standard cubic meters per minute
USGPS US gallons per second
USGPM US gallons per minute
USGPH US gallons per hour
USGPD US gallons per day
MUSGPD million US gallons per day
IGPS Imperial gallons per second
IGPM Imperial gallons per minute
IGPH Imperial gallons per hour
IGPD Imperial gallons per day
For Flow:
1. Select the upper and lower scale values in flow units.
2. Set the upper cal value to the pressure that will be asserted when the flow is to be the upper scale
value.
3. Set the lower cal value to the pressure that will be asserted when the flow is to be the lower scale
value.
4. Perform Cal Low and Cal high in pressure units only if required.
Calibration is optional and is done only if the factory or default calibration is not sufficient.