6. Maintenance/Repair
6.5. Replacing batteries
6.5 Replacing batteries
When to replace
When the transmitter displays a LOW BAT message you have 2-4 weeks to replace both batteries before
they expire. When batteries are removed or expired, all transmitter data is retained in the transmitter’s non-
volatile memory.
Tools required
40 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3
March 2012
#1 Phillips Screwdriver or 1/8” Slotted Screwdriver
Torque Screwdriver
1.5 mm hex key
Procedure
ATTENTION
Batteries must be replaced only by a trained service technician.
WARNINGS
Risk of death or serious injury by explosion. Do not open transmitter
enclosure when an explosive gas atmosphere is present.
Batteries must not be changed in an explosive gas atmosphere.
If IS Battery Pack, Honeywell 50047517-001, has been installed in the
Wireless Transmitter, the transmitter enclosure maybe opened when an
explosive gas atmosphere is present. Otherwise, do not open transmitter
enclosure when and explosive gas atmosphere is present.
- When not in use the Battery Pack must be stored in a non Hazardous
Area
The batteries used in this device may present a risk of fire or chemical
burn if mistreated. Do not recharge, disassemble, heat above 100°C
(212°F), or incinerate.
When installing batteries, do not snag the battery terminal on the clip or
the battery may be damaged. Do not apply excessive force.
Do not drop. Dropping the battery may cause damage. If a battery is
dropped, do not install the dropped battery into the transmitter. Dispose
of dropped battery promptly per local regulations or per the battery
manufacturer’s recommendations.