5. Operation
5.3. Transmitter PV display
Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual 23
March 2012
OneWireless User
Inteface display
Definition What to do
Transmitter
display
OVR LOAD Over Load
The applied pressure has
exceeded the limit
defined by the meter
body characterization
data.
Determine cause of over pressure.
CAL ERR Calibration Error
Calibration Data Invalid
or could not be read.
Use Cal Clear, Restore, or User
Calibrate.
LOW BAT Low Battery
Battery Voltage Critically
Low
Replace batteries as soon as
possible. See page 40.
LOW PWR Low Power
External Power Critically
Low
Check external 24V power supply
NO RADIO
Radio Interprocessor
Comm Error
Radio Board is not
accessible.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 38.
The following status messages have multiple meanings. Refer to OneWireless UI Device Status for exact cause.
INP FAIL Input Failure Input Error
Possible meter body sensor
failure.
INP FAIL A/D Failure
Diagnostics detected
defect with Analog to
Digital Converter.
Replace sensor module. See page
38.
E FAIL A/D Failure
Diagnostics detected
defect with Analog to
Digital Converter.
Replace sensor module. See page
38.
E FAIL Electronics Failure
Electronic Failure
detected on Sensor
Board. Could be caused
by one of the status
items marked by *.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 38.
E FAIL* NVM Fault*
Startup diagnostics
detected defect in
Sensor Non-Volatile
Memory
Replace sensor module. See page
38.
E FAIL* Program Memory Fault*
Startup diagnostics
detected defect in
Sensor Read Only
Memory
Replace sensor module. See page
38.
E FAIL* RAM Fault*
Startup diagnostics
detected defect in
Processor Random
Access Memory
Replace sensor module. See page
38.
The following statuses are displayed only in OneWireless UI Device Status.