5. Operation
5.3. Transmitter PV display
24 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3
March 2012
OneWireless User
Inteface display
Definition What to do
Transmitter
display
blank Excess Zero Calibration
The selected zero offset
or the lower calibration
trim point is beyond 5%
of the lower end of the
characterized range of
the device.
Clear Calibration
blank Excess Span Calibration
The calibrated upper and
lower trim has produced
a span that is greater
than 5% of the
characterized span of the
transmitter.
Clear Calibration
Or
Set Factory Calibration
Or
Check the applied trim points and
re-attempt lower and upper (trim)
calibration.
blank Excess Calibrated Range
The selected calibration
points used for upper
and lower trim are
outside the characterized
range of the transmitter.
Check that the upper and lower
trim points are both within the
characterized range of the
transmitter and re-attempt upper
and lower (trim) calibration.
blank Calibration Cleared
Indicates that both the
upper and lower trim
points as well as the zero
offset has been cleared.
The calibration source is
none.
Select Factory Calibration
Or
Calibration the zero offset
Or
Calibrate using the lower and
upper trim points.
blank*
Device/Firmware
Mismatch*
Sensor Board Firmware
Error. The software did
not pass verification
tests.
Replace sensor module. See page
38.
blank*
Heap Memory Not
Available*
Heap Allocation Failure.
Software detected heap
shortage and some
communication packets
may have been dropped.
Clear by warm restart of device. If
condition persists contact
Honeywell service.
blank* Watchdog Timer Error*
Sensor Watchdog
Timeout. The processor
was restarted due to
unexpected operation.
Clear by warm restart of device. If
condition persists contact
Honeywell service.