4 SPECIFICATIONS
• 4,3'' / 109,2 cm Touch-screen graphical color display, 480 x 272 pixel with back illumination and backlit membrane buttons
• One loop expandable to 2 loops with an optional expansion card
• Each loop manages up to 159 detectors plus 159 input/ output modules
• 16 Zones
• Fire and Fault C/NC/NO dry contacts relay
• 1 24 V DC, User load max. 500 mA
• 2 Digital Inputs
• Two sounder circuits load max. 250 mA each
• Output delays max. 10 minutes (according to EN 54)
• 10 Illuminated status LED: Power, Fire, Disablement, Test, Fault, System Fault, Earth Fault, Power Supply Fault, Aux Power Supply Output Fault, Sounder
Fault/Disablement
• 4 operating buttons: Reset Panel, Silence Buzzer, Silence Sounders, Evacuate
• 3 confirmations LED: Buzzer Mute, Sounder Stop, Evacuate
• 1 mechanical key
• The internal panel buzzer provides an audible alert to the authorized user, to take immediate action whenever the system detects any condition such as a fire or
fault event. Depending on the type of event, the buzzer activates (sounds) using a different tone pattern. The SILENCE BUZZER control button is used to silence
(mute) the internal buzzer after it has switched on following an event. This control is available at all access levels, without a need for PIN code
• AC power supply with different plug options with a max. rate power of 65 W
• Autonomy in standby and alarm time, in absence of main power, are based on the system configuration. Please refer to Honeywell Loop Calculator for more details
• Batteries: 2 x 12 V DC / 7 Ah
• Log and configuration through USB port type B, available in future releases
• Imin= 180 mA
• Imaxa= 380 mA
• Imaxb= 1,3 A
• Maximum RiMin = 0,63 Ohm
• Certified EN 54-2 / AC / A1
• Certified EN 54-4 / A1 / A2
• Certified LVD 62.368-1:2014+A11