Fire Alarm Control Panel PL-1000
M-169.1-SERIE-PL-EN / 09.2022 13
4.2 Electrical specifications
• External power supply: 100 ... 240 V AC, 50 ... 60 Hz
• AC Fuse: 4 A / 250 Vac / 5 x 20 mm (slow blow)
• Power consumption: max. 65 W
• 2 Supervised sounder outputs each with max. 250 mA
• 1 24 V DC, User load max. 500 mA
• 2 Digital Inputs
• 1 Alarm relay C/NC/NO dry contacts
• 1 Fault relay C/NC/NO dry contacts
• Max. 1.500 m distance depending on the cable section and current consumption in alarm
• Rmax battery: 1,4 Ohm
• Battery fuse: 4 A / 250 Vac / 5 x 20 mm (fast acting)
4.3 Environmental specifications
• Climate classification: K5 (IEC 721-2-3)
• Temperature range: -5 ºC ... 40 ºC
• Relative humidity: 5 % ... 95 % non-condensing
• Protection rating: IP 30 (acc. EN 60529)