31-00400M-01 | Rev10-20 13
TECHNICAL SPECIFICATIONS
IO Characteristics
Communication Baud Rates
Table 5 IO Characteristics
UIO x 2 Resistive Input
For 10K NTC type II, C7021 series
For 10K NTC type III,C7023 series
For 20K NTC, TR21 and C7041 series.
±0.5°C (±1°F) at 10 – 32°C (50 – 90°F)
±1.1°C (±2°F) at -1.1 – 50°C (30 – 122°F)
Voltage Input, SELV
0-10V, ±5% of full scale
Digital Input
Dry contact closure
Open circuit (≥ 100Kohms)
Closed circuit (≤100ohms)
Voltage Output
0-10V, ±3% of full scale @2K ohms
UI x 2 Resistive Input
for 10K NTC type II, C7021 series
for 10K NTC type III,C7023 series
for 20K NTC, TR21 and C7041 series
±0.5°C (±1°F) at 10 – 32°C (50 – 90°F)
±1.1°C (±2°F) at -1.1 – 50°C (30 – 122°F)
Voltage Input, SELV
0-10V, ±5% of full scale
Digital Input
Dry contact closure
Open circuit (≥ 100Kohms)
Closed circuit (≤100ohms)
DO (G,
Y1,Y2,Y3,W1,W
2,W3)
Relay Output
1 Amps Max. at 24VAC
DO (AUX) Relay Dry Contact
1 Amps Max. at 24VAC/DC
Table 6 Communication Baud Rates
BACnet IP Over Wi-Fi
Wi-Fi 802.11 b/g/n
Bluetooth BLE 4.2 with 1 Mbps
Classic Bluetooth with max. 3 Mbps

Other manuals for Honeywell TC500A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC500A and is the answer not in the manual?

Honeywell TC500A Specifications

General IconGeneral
BrandHoneywell
ModelTC500A
CategoryThermostat
LanguageEnglish

Related product manuals