CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
63-4528—04 110
Protection Parameters
Table 7. Protection Parameters
Parameter Explanation Settings
Factory
Setting
a
06-00 Low Voltage Level
230V: 160.0~220.0Vdc
460V: 320.0~440.0Vdc
180
360
a
06-01
Over-voltage Stall
Prevention
230V: 350.0~450.0Vdc
460V: 700.0~900.0Vdc
380.0
760.0
a
06-02
Over-current Stall
Prevention during
Acceleration
Heavy duty: 0~160%(100%: drive’s rated current);
Normal duty: 0~130%(100%: drive’s rated current)
Heavy duty:
120;
Normal duty:
120
a
06-03
Over-current Stall
Prevention during
Operation
Normal Load: 0~160%(100%: drive’s rated current);
Normal duty: 0~130%(100%: drive’s rated current)
Heavy duty:
120;
Normal duty:
120
a
06-04
Accel. /Decel. Time
Selection of Stall
Prevention at Constant
Speed
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
0
a
06-05
Over-torque Detection
Selection (OT1)
0: No function
1: Over-torque detection during constant speed operation,
continue to operate after detection
2: Over-torque detection during constant speed operation,
stop operation after detection
3: Over-torque detection during operation, continue to
operate after detection
4: Over-torque detection during operation, stop operation
after detection
0
a
06-06
Over-torque Detection
Level (OT1)
10~200%, 100%: drive's rated current
120
a
06-07
Over-torque Detection
Time (OT1)
0.0~60.0 seconds
0.1
a
06-08
Over-torque Detection
Selection (OT2)
0: No function
1: Over-torque detection during constant speed operation,
continue to operate after detection
2: Over-torque detection during constant speed operation,
stop operation after detection
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop operation
after detection
0
a
06-09
Over-torque Detection
Level (OT2)
10~200%, 100%: drive's rated current
120
a
06-10
Over-torque Detection
Time (OT2)
0.0~60.0 seconds
0.1
a
06-11 Maximum Torque Limit 0~250% (100%: drive’s rated current) 170%
a
06
-12
Electronic Thermal Relay
Selection (Motor 1)
0: Motor with constant torque output
1: Motor with variable torque output
2: Electronic Thermal Relay disabled
2
a
06-13
Electronic Thermal
Characteristic for Motor 1
30.0~600.0 seconds
60.0