CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
63-4528—04 114
Special Parameters
06-66
Bypass Fire Mode
enabled
0: Disable Bypass
1: Enable Bypass
0
06-67
Delayed Time when
Bypass Fire Mode
0.0 to 6550.0 sec 0
06-68
Auto reset counter of Fire
Mode
0~10 0
06-69
Length of time to reset
auto-counter (seconds)
0.0 to 6000.0 sec 600
Table 8. Special Parameters
Parameter Explanation Settings
Factory
Setting
a
07-00 Setup Software Brake Level
230V: 350.0~450.0Vdc
460V: 700.0~900.0Vdc
380.0
760.0
a
07-01 DC Brake Current Level 0~100% 0
a
07-02 DC Brake Time at Start-up 0.0~60.0 seconds 0.0
a
07-03 DC Brake Time at Stop 0.0~60.0 seconds 0.0
a
07-04
Startup Frequency for DC
Brake
0.00~600.00Hz
0.00
a
07-05
Restart after Momentary Power
Down
0: Stop operation
1: Speed search starting from last speed before the moment
of power down.
2: Speed search starting from minimum output frequency
1
a
07-06 Maximum Power Loss Duration 0.1~20.0 seconds 2.0
a
07-07 Base Block Time 0.1~5.0 seconds 0.5
a
07-08 Current Limit for Speed Search 20~200% 100
a
07-09
Base Block Speed Search (oc,
ov, bb)
0: Stop operation
1: Speed search starting from last speed before the moment
of base block.
2: Speed search starting from minimum output frequency
0
a
07-10
# of Auto Reset after Errors
Occurred
0~10
0
a
07-11 Speed Search while Start-up
0: Disable
1: Speed search starting from maximum output frequency
2: Speed search starting from start-up motor frequency
3: Speed search starting from minimum output frequency
0
Table 7. Protection Parameters
Parameter Explanation Settings
Factory
Setting