CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
153 63-4528—04
When output current is larger or equal to Pr.02-31, it will activate multi-function output terminal (Pr.02-13, 02-14, 02-16, and
02-17 is set to 27).
When output current is smaller than Pr.02-31, it will activate multi-function output terminal (Pr.02-13, 02-14, 02-16, 02-17 is set
to 28).
When output frequency is higher than Pr.02-32, it will activate the multi-function terminal (Pr.02-13, 02-14, 02-16, 02-17 is set
to 29).
When output frequency is lower than Pr.02-32, it will activate the multi-function terminal (Pr.02-13, 02-14, 02-16, 02-17 is set
to 30).
Setting 1:
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will run.
Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON, the drive can run after
pressing RESET key.
a
02 - 31 Output Current Level Setting for Multi-function Output Terminals
Factory Setting: 0
Settings 0~100%
a
02 - 32 Output Boundary for Multi-function Output Terminals
Factory Setting: 0.00
Settings 0.00~±60.00Hz
a
02 - 33 External Operation Control Selection after Reset and Activate
Factory Setting: 0
Settings 0: Disable
1: Drive runs if the run command still exists after reset or re-boots.