CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 154
a
02 - 36 Expansion Card Output Terminal (MO3)
a
02 - 37 Expansion Card Output Terminal (MO4)
a
02 - 38 Expansion Card Output Terminal (MO5)
a
02 - 39 Output terminal of the I/O extension card (MO6)
a
02 - 40 Output terminal of the I/O extension card (MO7)
a
02 - 41 Output terminal of the I/O extension card (MO8)
a
02 - 42 Output terminal of the I/O extension card (MO9)
a
02 - 43 Output terminal of the I/O extension card (MO10)
a
02 - 44 Output terminal of the I/O extension card (MO11)
Factory Setting: 0
Settings:
0: No function
1: Operation Indication
2: Operation speed attained
3: Desired Frequency Attained 1 (Parameter 02-20)
4: Desired Frequency Attained 2 (Parameter 02-22)
5: Zero speed (Frequency command)
6: Zero speed, include STOP (Frequency command)
7: Over torque 1
8: Over torque 2
9: Drive is ready
10: Low voltage warning: LV (Pr.06-00)
11: Malfunction indication
12: Mechanical brake release (Pr.02-30)
13: Overheat warning (Pr.06-14)
14: Software brake signal indication (Pr.07-00)
15: PID feedback error
16: Slip error (oSL)
17: Terminal count value attained, does not return to 0
(Pr.02-18)
18: Preliminary count value attained, returns to 0 (Pr.02-17)
19: Base block
20: Warning output
21: Over voltage warning