EasyManua.ls Logo

HP 6100

HP 6100
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 53 EVA 6x00 UPS loading (continued)
% of UPS capacity
WattsEnclosures
R12000R5500R3000
20.554.691.124606
17.346.277.220835
14.237.963.217074
11.129.549.313303
7.921.235.39532
4.812.821.45771
Table 54 EVA 4x00 UPS loading
% of UPS capacity
WattsEnclosures
R3000R1500
60.616374
46.694.012603
32.765.98832
18.737.95071
Environmental specifications
Table 55 Environmental specifications
50° to 9 F (1 to 3 C) - Reduce rating by F for each 1000 ft. altitude (1.8°
C/1,000 m)
Operating temperature
-4 to 150° F (-40° to 6 C)Shipping temperature
10% to 90% non-condensingOperating humidity
5% to 90% non-condensingShipping humidity
Up to 8,000 ft. (2,400 m)Altitude
Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or largerAir quality
148 Non-standard rack specifications

Table of Contents

Other manuals for HP 6100

Related product manuals