Table 11: Electrical Requirements
Specification (for each PSU)Component
HPE Alletra 6010, 6030, 6050 (Regulatory model number NMBLA-0003-800)
800 W power supply (LITE-ON-HSTNS-PL41-1)
AC input voltage: 100-240V
Maximum rated input current: 9.4-4.5 A
Rated input frequency: 50-60 Hz
IEC 60320 C14 connector
HPE Alletra 6030, 6050, 6070, 6090 (Regulatory model number NMBLA-0003-1600)
1600 W AC power supply (ASTEC HSTNS-PR62)
AC input voltage: 200-240V
Maximum rated input current: 8.7A
Rated input frequency: 50-60 Hz
IEC 60320 C14 connector
1600 W DC power supply (Delta HSTNS-PD70)
DC input voltage: -40 to -72V, no tolerance
Maximum rated input current: 45A
HPE Alletra 2140 expansion shelf (Regulatory model number NMBLA-0003-800E)
800 W power supply
AC input voltage: 100-240V
Maximum rated input current: 9.4-4.5 A
Rated input frequency: 50-60 Hz
IEC 60320 C14 connector
HPE Alletra 2140 expansion shelf rating, configuration and warning information is based on
IEC 62368-1.
Power supplies
800 W power supply: IEC 60320 C14 connector
1600 W AC power supply: IEC 60320 C14 connector
Power supply connectors
Type varies by region.Power cords
Installation of this equipment must comply with local and regional electrical regulations governing the installation of information
technology equipment by licensed electricians. This equipment is designed to operate in installations covered by Article 645
of the National Electrical Code and NFPA 75.
Model Specifications
The latest specifications for the HPE Alletra 6000 storage arrays can be found on the HPE website at:
https://infosight.hpe.com/InfoSight/media/local/active/100/HPE%20Alletra%206000%20Config%20Matrix.pdf .
Hardware and Model Specifications 123