PrecautionConsideration
Mount the equipment so that the mechanical loads on the rack are even top-to-bottom, front-to-back,
and side-to-side.
Mechanical Load-
ing
Be sure there is adequate power service to prevent overloading the circuits. Check the ratings of each
item of equipment on each circuit.
Note: The power supplies are 220VAC or 110VAC auto-detecting.
Circuit Overloading
You must provide reliable grounding (earthing) of rack-mounted equipment. In addition, pay attention
to supply connections from the branch circuit, such as power strips.
Reliable Grounding
Install the Array
Use this procedure to install the following array models: HPE Alletra 6010, 6030, 6050, 6070, and 6090.
Before you begin
Attention:
If you are installing more than one storage array, refer to the Hardware Guide available on HPE InfoSight for information
about your model.
https://infosight.hpe.com/org/c2165d17-4d55-4954-83e3-60556a7bb6c8/resources/nimble/docs
What you need for each array:
19-inch four-post rack. The provided rails fit both round-hole and square-hole racks.
4U space available in the 19-inch rack
At least two Ethernet cables for management, one cable per controller
At least two cables, Ethernet or Fibre Channel, for data
One or two switches, depending on your array and network topology. Two 10GbE or Fibre Channel switches are
recommended for high availability and redundancy.
Four power outlets, two per controller, on separate circuits
Current for 800 W power supplies with C14 connectors:
Steady state current (approximate): 5.6A @ 240V; 11.7A @120V
Startup current (approximate): 4.6A @ 240V; 10.3A @ 120V
Current for 1600 W power supplies with C14 connectors (240V only):
Steady state current (approximate): 8.9A @ 240V
Startup current (approximate): 8.2A @ 240V
Before beginning, download and read the Release Notes, available on HPE InfoSight (https://infosight.hpe.com). If you do not
have an HPE InfoSight account, click Create Account and provide the required information.
Visit the Welcome Center (http://www.hpe.com/support/storage-welcomecenter) for help setting up your HPE storage array.
Before you can start using the array, you must register the array with Data Services Cloud Console. If you do not have an HPE
GreenLake cloud account (https://common.cloud.hpe.com), the Welcome Center can guide you.
Note:
Install this product in restricted-access locations only, such as a dedicated equipment room or an electrical closet.
Installation and maintenance must be carried out by qualified personnel.
Position the rack in a location with at least 800 mm rear clearance and 1000 mm front clearance for maintenance
access.