d) Pull the release levers down until they stop. The expander ejects slightly from the chassis.
e) Supporting the weight of the expander, pull the release levers to slide the expander out of the chassis. Then place the
expander on a flat surface.
Important:
To avoid electrostatic damage, place array components on a grounded anti-static mat. Use an ESD wrist strap
during removal and replacement.
3. Move the power supplies from the failed expander to the new expander.
a) Push the power supply release lever to the left, grasp the handle, and pull the power supply out of the bay.
21 Power supply handlePower supply release lever
b) Slide the power supply into a bay of the new expander until it clicks into place.
c) Repeat this action with the other power supply. A power supply can be installed in either bay of the new expander.
4. Install the replacement expander.
a) Make sure the release levers are fully extended.
b) Slide the expander into the chassis bay. If it does not slide in easily, remove it and try again.
c) After the expander is in place, return the release levers to their original closed position, and then tighten the
thumbscrews.
d) Reconnect the network cables to the expander (as labeled from step 2).
e) Reconnect the power cables to both power supplies.
5. Verify that the new expander is powered on.
After it is installed, the expander powers on automatically. The LEDs on the expansion shelf light solid green. If the expander
does not power on automatically, contact HPE Support.
Note: The new expander might take up to 15 minutes to appear in the user interface. If the expander takes longer
than 15 minutes to report an Active/Standby state, contact HPE Support for assistance.
6. Return the failed expander as directed on the RMA work order.
Power Supply Maintenance
The procedures for maintaining power supplies is the same for all storage arrays and expansion shelf models.
Replace an AC Power Supply
Use this procedure to replace a failed AC power supply unit (PSU) on your HPE storage array or expansion shelf.
Before you begin
5 to 10 minutesTime required:
Replacement AC power supply ordered from HPEParts required:
Maintenance Procedures 93