HP UPS Network Module web interface 37
Item Description
1
Battery capacity
2
Time
3
Utility failure
4
Shutdown initiated
5
Load segment powered down
6
Low battery
7
Battery depleted
8
Operating system shutdown time
9
Shutdown initiated after time
iii. In the Shutdown initiated if battery capacity under field (individual load segments), enter the
minimum amount of battery life that can remain before the load segment shutdown sequence
starts (0 to 100%, 20% by default). The UPS Network Module initiates a load segment shutdown
when the remaining battery life reaches the specified percentage.
NOTE: This parameter can initiate the shutdown sequence before the shutdown delay expires.