Troubleshooting 76
Bits per second9600
Data bits—8
Parity—None
Stop bits—1
Flow controlNone
The default password to access the serial configuration menu is “admin”.
UPS Network Module fails to boot after upgrading the
firmware
Possible Cause: The application might be corrupted due to an interruption while flashing the firmware.
Action:
1. Using the supplied serial cable, connect to the UPS Network Module through a terminal emulation
program, such as HyperTerminal, with the following parameters:
o Bits per second9600
o Data bits—8
o Parity—None
o Stop bits—1
o Flow controlNone
In the HyperTerminal window, the UPS Network Module Bootloader prompts for a TFTP IP address.
2. Setup a TFTP server.
3. Copy the UPS Network Module firmware image file to the TFTP server default folder.
4. Rename the UPS Network Module image file to image.bin.
5. Launch the TFTP.
6. Enter the TFTP server IP address at the prompt on the terminal emulation program window.
7. Press Enter.
UPS is not powered on after a scheduled shutdown
Possible cause: The Restart time value might be configured as less than the Shutoff time value.
Action: Configure the Restart time to a greater value than the Shutoff time value.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP UPS Network Module and is the answer not in the manual?

HP UPS Network Module Specifications

General IconGeneral
BrandHP
ModelUPS Network Module
CategoryNetwork Hardware
LanguageEnglish

Related product manuals