Connecting the serial communications port
CAUTION: Use only the computer interface cable supplied with the UPS to connect the communications
port to the host computer.
IMPORTANT: Power protector software requires the communications port to be appropriately cabled to
the host computer.
NOTE: This port is only used for firmware upgrades. To update the UPS firmware, see the Hewlett Packard
Enterprise website.
Connecting the RPO port
WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS
installed in a computer equipment room must be connected to an RPO circuit.
IMPORTANT: The remote switch must be in the Off (open) position to enable power to the output
receptacles.
NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or equivalent).
Separate wire pairs are attached to a single, normally open contact in a parallel connection. Hewlett Packard
Enterprise recommends using different colors for the positive and negative wires.
If a connector becomes disconnected and is reconnected with reversed polarity, an RPO is initiated. To avoid
RPO port disconnect:
18 Installation

Table of Contents

Other manuals for HPE G2 R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R5000 and is the answer not in the manual?

HPE G2 R5000 Specifications

General IconGeneral
Power Capacity5000 VA / 4500 W
Input Voltage200-240 VAC
Output Voltage200-240 VAC
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 VAC
Nominal Input Voltage230 VAC
Frequency50/60 Hz
Form FactorRackmount
InterfaceUSB, Serial
Operating Temperature0°C to 40°C
Operating Humidity0 to 95% RH non-condensing
Weight30 kg