Troubleshooting
Bypass mode
Symptom
LED is on.
Cause
An overload or a fault has occurred.
A command has been received and the UPS is in Bypass mode.
Action
1. Equipment is powered but not protected by the UPS.
2. Check one of the following alarms.
Overtemperature
Overload
UPS failure
Battery low
Symptom
LED is on, one beep for every three seconds.
Cause
The UPS is in Battery mode and the battery is running low.
Action
1. The warning is approximate, and the actual time to shutdown may vary significantly.
2. Depending on the UPS load and number of ERMs, the battery low warning might occur before the
batteries reach 20% capacity.
No battery
Symptom
LED is on, continuous beep.
Cause
The batteries are disconnected.
Troubleshooting 31

Table of Contents

Other manuals for HPE G2 R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R5000 and is the answer not in the manual?

HPE G2 R5000 Specifications

General IconGeneral
Power Capacity5000 VA / 4500 W
Input Voltage200-240 VAC
Output Voltage200-240 VAC
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 VAC
Nominal Input Voltage230 VAC
Frequency50/60 Hz
Form FactorRackmount
InterfaceUSB, Serial
Operating Temperature0°C to 40°C
Operating Humidity0 to 95% RH non-condensing
Weight30 kg

Related product manuals