Action
1. Verify that all batteries are properly connected.
2. If condition persists, contact your service representative.
Battery fault
Symptom
LED is on, continuous beep.
Cause
The battery test failed due to bad or disconnected batteries.
The battery minimum voltage is reached and the UPS is in ABM cycling mode.
Action
1. Verify that all batteries are properly connected.
2. Start a new battery test.
If condition persists, contact your service representative.
Backup time
Symptom
The UPS does not provide the expected backup time.
Cause
The batteries need charging or service.
Action
1. Apply utility power for 48 hours to charge the batteries.
2. If condition persists, contact your service representative.
Bypass mode
Symptom
LED is on.
Cause
An overload or a fault has occurred.
A command has been received and the UPS is in Bypass mode.
32 Troubleshooting

Table of Contents

Other manuals for HPE G2 R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R5000 and is the answer not in the manual?

HPE G2 R5000 Specifications

General IconGeneral
Power Capacity5000 VA / 4500 W
Input Voltage200-240 VAC
Output Voltage200-240 VAC
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 VAC
Nominal Input Voltage230 VAC
Frequency50/60 Hz
Form FactorRackmount
InterfaceUSB, Serial
Operating Temperature0°C to 40°C
Operating Humidity0 to 95% RH non-condensing
Weight30 kg

Related product manuals