Table 1: G2 R5000 battery runtimes
Load % Estimated battery
runtime (minutes)
Runtime with one ERM
(minutes)
Runtime with four
ERMs (minutes)*
10 73 245 931
20 42 149 559
40 17 69 250
60 9 39 144
80 5 25 103
100 3 20 80
Table 2: G2 R6000 battery runtimes
Load % Estimated battery
runtime (minutes)
Runtime with one ERM
(minutes)
Runtime with four
ERMs (minutes)*
10 57 202 753
20 34 125 448
40 14 57 194
60 7 32 116
80 5 22 84
100 3 16 58
Environmental specifications
Feature Specification
Operating temperature 0ºC to 40ºC (32ºF to 104ºF)
Nonoperating
temperature
• With batteries—0ºC to 40ºC (32ºF to 104ºF)
• Without batteries—-15ºC to 60ºC (5ºF to 140ºF)
Relative humidity 0-95% non condensing
Operating altitude Up to 3,000m (9,843ft) above sea level
Nonoperating altitude Up to 10,000m (32,808ft) above sea level
Audible noise Less than 45 dBA, normal operation
RPO port specifications
The RPO port meets the requirements of NFPA Articles 645-10 and 645-11 for a Disconnecting Means.
Specifications 37