In ABM mode, the ABM cycle is restarted after the test is complete.
In constant charge mode, the charging phase is restarted after the test is complete.
Manual battery full test
The manual battery test is run immediately, even if the UPS is operating in ABM mode, and no test is
postponed or scheduled to run in float mode.
ABM mode—the ABM cycle is stopped, the test is performed, and then the ABM cycle is restarted after the
test is complete.
Constant charge mode—The charging phase is restarted after the test is complete.
Starting power to the load
Start power to the load by placing the UPS in Operate mode.
IMPORTANT: AC power must be available the first time the UPS is started.
Installing the ERM
Before installing the ERM, review and observe all warnings in Precautions.
WARNING: A risk of personal injury or damage to the equipment exists. Uneven loading of equipment in
the rack might cause the rack to become unstable. Install the heavier components first, and then
continue to populate the rack from the bottom to the top.
Procedure
1. Install the mounting rails.
2. With one person on each side of the carton, lift the chassis and lower it to the floor in front of the rack.
3. Install the mounting ears on the chassis using the screws provided.
Installation 23

Table of Contents

Other manuals for HPE G2 R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE G2 R5000 and is the answer not in the manual?

HPE G2 R5000 Specifications

General IconGeneral
Power Capacity5000 VA / 4500 W
Input Voltage200-240 VAC
Output Voltage200-240 VAC
Battery TypeSealed Lead-Acid (SLA)
Nominal Output Voltage230 VAC
Nominal Input Voltage230 VAC
Frequency50/60 Hz
Form FactorRackmount
InterfaceUSB, Serial
Operating Temperature0°C to 40°C
Operating Humidity0 to 95% RH non-condensing
Weight30 kg

Related product manuals