EasyManua.ls Logo

HPE SN6500B

HPE SN6500B
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Facility requirements
Table 15: Facility requirements
Dimension Value
Electrical Adequate supply circuit, line fusing, and wire size, as specified by the
electrical rating on the switch nameplate
Circuit protected by a circuit breaker and grounded in accordance
with local electrical codes
See HPE StoreFabric SN6500B 16Gb FC Switch power supply
specifications for complete power supply specifications.
Thermal Minimum airflow of 79.8 cubic m/hr (47 cubic ft/min) available in the
immediate vicinity of the switch
Ambient air temperature not exceeding 40°C (104°F) while the
switch is operating
Cabinet (rack mounted)
Use rack kits designed for the
extra width of the switch to
mount in standard cabinets/
racks.
1U in a 48.3 cm (19 in) cabinet
All equipment in cabinet grounded through a reliable branch circuit
connection
Plenum installed to prevent overheating
Additional weight of switch not to exceed the cabinet’s weight limits
Cabinet secured to ensure stability in case of unexpected movement
Power supply specifications
The power supplies are universal and operate worldwide without voltage jumpers or switches. They meet
IEC 61000-4-5 surge voltage requirements and support autoranging to accommodate input voltages and
line frequencies. Each power supply has built-in fans for cooling.
Table 16: HPE StoreFabric SN6500B 16Gb FC Switch power supply specifications
Specification Values
Input voltage Range: 90–264 VAC Auto-volt, Nominal: 100–240 VAC, 12.0-5.0 A;
47-63 Hz
The switch autosenses input voltage
Startup: 80–87 VAC; Turn-off: 85–75 VAC
Input frequency Range: 47–63 Hz; Nominal: 50–60 Hz
Inrush current Maximum of 40 A peak at 240 VAC during cold startup at 25ºC
ambient
Input line protection Both AC lines are fused
Maximum power supply output
(each)
1,080 W at 12 VDC
78 Facility requirements