6.1.3 d02: Analogue Status Display Parameters
Ref. Code Function Description Setting Range [Default]
d02.00 AI1 voltage [Actual value]
Display AI1 input voltage.
d02.01 AI1 voltage (after calculating) [Actual value]
Display A1 input voltage which is calculated by the gain, bias and filter.
d02.02 AI2 voltage [Actual value]
Display AI2 input voltage.
When selects current input, -10.00V corresponds to 0mA, and 10.00V corresponds to 20mA.
d02.03 AI2 voltage (after calculating) [Actual value]
Display AI2 input voltage which is calculated by the gain, bias and filter.
d02.04 AI3 voltage [Actual value]
Display AI3 input voltage.
When selects current input, -10.00V corresponds to 0mA, and 10.00V corresponds to 20mA.
d02.05 AI3 voltage (after calculating) [Actual value]
Display AI3 input voltage which is calculated by the gain, bias and filter.
d02.06 AI4 voltage [Actual value]
Display AI4 input voltage.
When selects current input, -10.00V corresponds to 0mA, and 10.00V corresponds to 20mA.
d02.07 AI4 voltage (after calculating) [Actual value]
Display AI4 input voltage which is calculated by the gain, bias and filter.
d02.08 AO1 output [Actual value]
Display AO1 output.
When selects current output, 0V corresponds to 0mA, and 10.00V corresponds to 20mA.
d02.09 AO2 output [Actual value]
Display AO2 output.
When AO2 selects current output, 0V corresponds to 0mA, and 10.00V corresponds to 20mA.