Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
HD3L Series Controller User Manual 63
6.2.12 F14: SCI Communication Parameters
Ref. Code Function Description Setting Range [Default]
F14.00 Data format 0 - 5 [0]
0: 1-8-2 format, no parity, RTU.
1: 1-8-1 format, even parity, RTU.
2: 1-8-1 format, odd parity, RTU.
3: 1-7-2 format, no parity, ASCII.
4: 1-7-1 format, even parity, ASCII.
5: 1-7-1 format, odd parity, ASCII.
F14.01 Baud rate 0 - 5 [3]
0: 1200bps.
1: 2400bps.
2: 4800bps.
3: 9600bps.
4: 19200bps.
5: 38400bps.
F14.02 Local address 0 - 247 [2]
F14.02 = 0, it means broadcast address.
F14.03 Host PC response time 0 - 1000 [0ms]
F14.04 Detection time of communication timeout 0.0 - 1000.0 [0.0s]
Time at no communication data > setting time of F14.04, it will be considered as E0028 fault (SCI timeout
fault).
F14.04 = 0, it will not detect communication timeout.
F14.05 Detection time of communication error 0.0 - 1000.0 [0.0s]
Time at communication error > setting time of F14.05, it will be considered as E0029 fault (SCI fault).
F14.05 = 0, it will not detect the communication error.
F14.06 - F14.47 Unused
6.2.13 F15: Display Control Parameters
Ref. Code Function Description Setting Range [Default]
F15.00 Language selection 0 - 9 [0]
Defines the displaying language on the LCD keypad.
0: Chinese.
1: English.
2 - 9: Unused.
F15.01 Display contrast of the LCD keypad 1 - 10 [5]
To select LCD display contrast.
F15.02 Set parameter 1 of run status 0 - 32 [5]
F15.03 Set parameter 2 of run status 0 - 32 [6]
F15.04 Set parameter 3 of run status 0 - 32 [10]
F15.05 Set parameter 4 of run status 0 - 32 [11]
F15.06 Set parameter 5 of run status 0 - 32 [0]
F15.07 Set parameter 6 of run status 0 - 32 [0]
F15.08 Set parameter 1 of stop status 0 - 32 [4]
F15.09 Set parameter 2 of stop status 0 - 32 [14]
F15.10 Set parameter 3 of stop status 0 - 32 [16]
6