Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
68 HD3L Series Controller User Manual
6.2.16 F18: PWM Parameters
Ref. Code Function Description Setting Range [Default]
F18.00 Carrier frequency 1 - 16kHz [Depend on HD3L]
Defines the carrier frequency of PWM output wave.
Controller power Setting range Factory setting
2.2 - 22kW 1 - 16kHz 8kHz
30 - 45kW 1 - 12kHz 6kHz
The carrier frequency will affect the operating noise of the motor. The higher the carrier frequency, the
lower the noise made by the motor. Please properly set the carrier frequency.
When the value is higher than the factory setting, HD3L should be derated by 5% when per 1kHz is
increased compared to the factory setting.
F18.01 Carrier freqency auto adjust selection 0,1 [0]
0: Unused.
1: Enable.
F18.02 PWM overmodulation enable 0,1 [1]
0: Disabled.
1: Enable.
F18.03 PWM overmodulation mode 0,1 [0]
0: Two phase / Three phase swtich.
1: Three phase.
6.3 Group Y: Manufacturer Parameters
The Group y is the manufacturer parameters group for commissioning at the factory before delivery.