Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd.
52 HD3L Series Controller User Manual
Ref. Code Function Description Setting Range [Default]
F05.16 Speed within FAR range 0.0 - 20.0 [1.0%]
The pulse signal will output if elevator speed is
within the FAR range. As shown in the right
figure.
F05.17 Over-speed setting 80.0 - 120.0 (F00.02) [115.0%]
F05.18 Over-speed detection time 0.0 - 2.0s [0.2]
When the actual elevator speed exceeds F05.17 and the duration time exceeds F05.18, HD3L alarms E0032
fault (motor over speed).
F05.18 = 0, HD3L does not detect motor over speed fault.
F05.19 Detection value of speed deviation 0.0 - 30.0 (F00.02) [20.0%]
F05.20 Detection time of speed deviation 0.0 - 2.0 [1.0s]
When the deviation of setting speed (after Acc / Dec) and actual run speed of motor exceeds F05.19 and the
duration time exceeds F05.20, HD3L alarms E0018 fault (excessive speed deviation).
F05.19 or F05.20 = 0, HD3L does not detect the excessive speed deviation fault of motor.
F05.21 Unused
F05.22 Creeping speed 0.000 - 0.400 [0.050m/s]
Defines the running speed at the forced Dec run.
F05.23 - F05.25 Unused
F05.1
6
F05.1
6
Elevator speed
DO
Setting speed
Setting speed+F15.16
Setting speed-F15.16
Time
Time