Shenzhen Hpmont Technology Co., Ltd. Chapter 6 Function Introduction
HD3L Series Controller User Manual 65
Ref. Code Function Description Setting Range [Default]
F16.04 Fan control delay time 0.0 - 600.0 [30.0s]
F16.05 Brake unit action voltage 380 - 750V [Depend on HD3L]
For 380V voltage class controller, the braking voltage range is 630 - 750V.
For 220V voltage class controller, the braking voltage range is 380 - 450V.
Note: The braking action enables only in run status of HD3L.
F16.06 Detection time of contactor fault 0.1 - 10.0 [2.0s]
F16.07 Multi-speed inspection 0 - 7 [0]
When the DI terminals are not enough, the MS1 - MS3 can achieve inspection run.
DI terminal = INS (No. 7 function), only need set F16.07 as 0 to enter terminal inspection run.
DI terminal ≠ INS (No. 7 function), the inspection run can be achieved via the MS1 - MS3.
Value of MS1 - MS3 = value of F16.07, enter MS inspection run at MS run speed (F05.00 - F05.07).
Note: When MS run speed (F05.00 - F05.07) exceeds 0.630m/s, run at 0.630m/s.
F16.08 Zero-speed threshold 0.001 - 0.010 [0.003m/s]
When the present run speed ≤ F16.08, the system run speed will be considered as 0. After zero-speed delay
signal, the zero-speed signal will output.
F16.09 Selection at motor overheat fault 0,1 [0]
0: When detect that the motor is overheated, alarm E0020 fault (motor overheat) after motor stops.
1: When detect that the motor is overheated, alarm E0020 fault (motor overheat) at once.
F16.10 - F16.11 Unused
F16.12 Delay time of run output signal 0.00 - 1.00s [0.00s]
Note: F16.12 is used to delay the controller running signal (output = No. 2 function)
so as to control the HD3L to
open the brake.
F16.13 UPS running direction auto-determine enable 0,1 [0]
0: Not enable.
1: Enable.
In UPS mode, HD3L will not run in the direction given by the terminal and auto-detemine the the
elevator light-load running direction.
In the UPS mode, HD3L will automatically up, and down, and then run according to the light-load
direction of detemining.
F16.14 Running min. current limit 0 - 100 (F07.11) [20%]
F16.15 Running min. detection time 0.0 - 5.0 [0.0s]
When the elevator run current is less than F16.14 and duration exceeds F16.05, HD3L alarms E0025 fault (too
small running current).
F16.16 Governor fault detection time 0.0 - 2.0 [1.0s]
When the governor detection terminal detects the duration of signal reaches F16.16, HD3L alarms E0037
fault (governor fault).
F16.17 DC braking current at stop 0 - 150 [100%]
F16.18 Starting frequency of DC braking current at stop 0.20 - 10.00 [0.50Hz]
F16.19 Brake release frequency 0.00 - 10.00 [0.00Hz]
F16.20 - F16.24 Unused