Determine whether land transportation requirements are met:
● Pavement condition: highway and country road with solid subgrade and damaged
pavement covering layer, which can be a gravel road, earth-rock road, or concrete or
asphalt road which has not been maintained for a long time; road that has concave pits
with a diameter of 10–15 mm irregularly distributed, the length of the road taking up
more than 60% of the total length. Corrugation waves are allowed on the road, with the
wave distance of 750–1000 mm and wave crest height of 25–50 mm.
● Test standard: trac running test for more than 480 km (speed: 30–40 km/h);
emergency brake for six times at a speed of 30 km/h (emergency brake twice at a 30-
degree gradient when going down a slope). After all tests are performed, there are no
obvious damages, such as getting loose or cracks. After power-on, the performance
specications of all components are consistent with the test data before transportation.
Cost-Eectiveness and High Energy Eciency
● The pre-fab. module integrates the cooling system, power distribution system,
monitoring system,
re extinguishing system, and cabinets that are pre-
installed and pre-commissioned before delivery. The pre-fab. module goes
through the trial run before delivery. Customers are welcome to check and try
the product in the factory.
● Civil engineering is simple when the data center is deployed outdoors. It starts
to work after being installed on a concrete podium or platform and connected
to a
humidier, water supply, mains power supply, and network.
● Mature delivery mode, modular structure, and low-cost transportation of the
pre-fab. module ensure fast deployment, and simple and convenient
expansion and upgrade.
● The FusionDC1000 is
energy-ecient. The hot and cold aisles are separated in
the equipment compartment to ensure high cooling
eciency.
Intelligent Management
● Manages the infrastructure of the data center in a central manner.
● Supports O&M using a mobile app and remote unattended operations. Full
WiFi coverage is implemented inside the pre-fab. module using a WiFi
module. WiFi coverage outside the pre-fab. module is implemented using a
customer router gateway.
● Monitors equipment
eectively in real time.
● Monitors environments in real time to identify potential risks.
● Provides various methods of collecting and analyzing power consumption
data to realize precision energy
eciency analysis. Such data is fundamental
to improving the power usage eectiveness (PUE). You can customize the
data collection and analysis methods.
● Provides a robust security mechanism to protect equipment and ensures a
proper environment.
● Provides standard Simple Network Management Protocol (SNMP) ports to
communicate with third-party network management systems (NMSs).
Intelligent Features
● Local PAD 3D NMS + app view, power supply/cooling 2D link visibility inside
the pre-fab module.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 1 Overview
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 3