Parameter Name Description
Shutdown
at high
feed-in
power
a
Shutdown at high feed-in power ● The default value is Disable.
● If this parameter is set to Enable,
the inverter shuts down for
protection when the grid-
connection point power exceeds
the threshold and remains in this
condition for the
specied time
threshold.
Upper feed-in power threshold for inverter
shutdown (kW)
● The default value is 0. This
parameter species the power
threshold of the grid-connection
point for triggering inverter
shutdown.
High feed-in power duration threshold for
triggering inverter shutdown (s)
The default value is 20. This
parameter species the duration
threshold of high feed-in power for
triggering inverter shutdown.
● When High feed-in power
duration threshold for triggering
inverter shutdown is set to 5,
Shutdown at high feed-in power
takes precedence.
● When High feed-in power
duration threshold for triggering
inverter shutdown is set to 20,
Grid connection with limited
power takes precedence (when
Active power control is set to
Grid connection with limited
power).
Note a: This parameter is supported only for the AS4777 grid code.
----End
7.2.1.2 Apparent Power Control on the Inverter Output Side
On the home screen, tap Settings > Power adjustment to set inverter
parameters.
SUN2000-(2KTL-6KTL)-L1
User Manual 7 Man-Machine Interaction