Page #93 background imageLoading...
Page #93 background image
IPS Test Type Description
Maximum
overfrequency
(81.S1)
The default overfrequency protection threshold is 50.2 Hz,
and the default protection time threshold is 0.1s.
Maximum
overfrequency
(81.S2)
The default overfrequency protection threshold is 51.5 Hz,
and the default protection time threshold is 0.1s.
Minimum
underfrequency
(81.S1)
The default underfrequency protection threshold is 49.8 Hz,
and the default protection time threshold is 0.1s.
Minimum
underfrequency
(81.S2)
The default underfrequency protection threshold is 47.5 Hz,
and the default protection time threshold is 0.1s.
Step 3 After the IPS test is complete, IPS State is displayed as IPS state success. Tap
Historical report in the upper right corner of the screen to view the IPS check
report.
----End
7.2.4 DRM (Australia AS4777)
Function
According to Australia AS 4777.2-2015, solar inverters need to support the
function of demand response mode (DRM), and DRM0 is a mandatory
requirement.
This function is disabled by default.
Figure 7-18 Wiring diagram for the DRM function
NO TE
The demand response enabling device (DRED) is a power grid dispatch device.
SUN2000-(2KTL-6KTL)-L1
User Manual 7 Man-Machine Interaction
Issue 10 (2023-02-13) Copyright © Huawei Technologies Co., Ltd. 86

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-3KTL-L1 and is the answer not in the manual?

Huawei SUN2000-3KTL-L1 Specifications

General IconGeneral
Max. efficiency98.4%
Max. input voltage600 V
Nominal output power3000 W
Dimensions (W x H x D)365 x 365 x 156 mm
Operating temperature range-25°C to +60°C
Nominal AC voltage220 V / 230 V / 240 V
MPPT voltage range90 V - 560 V
Rated input voltage360 V
Number of MPPTs2
CoolingNatural Convection
Protection degreeIP65
Rated output voltage220 V / 230 V / 240 V
Output frequency50 Hz / 60 Hz
Power factor0.8 leading ... 0.8 lagging
THDi<3%
Efficiency98.4%
Warranty10 years
Max. apparent AC power3300 VA
Max. output power3300 W