34
Power-on Settings - Denes power-on state of dimmers that do not have a photocell
congured. Dimmers can be set to zero or maximum level or to the last dimming level when
power was removed then re-applied.
• Once the POWER-ON SETTINGS is selected, scroll to the Dimmer that will need to
change the power–on state and choose the appropriate Function,(F), key button.
o Zero - Open circle,F1 - >Full Dim
o Last - Half lled circle, F2 –>return to the dimmed state prior to power removal.
o MAX – Filled circle, F3 –> Full Bright
o Save- F4 -> Save settings a return to Dimming Main Menu.
System Tools
The following programming selections are available in the System Tools Menu:
• Manual Control
• System Status
• Save/Restore Program
• Priorities/Masking
• Access Control
• Diagnostics
• Update Firmware
• Controller Version
• Relay Version
• Reboot System
Manual Control
The Manual Control function allows for manual operation and testing of panel components and programming. The Manual Control
Menu allows the user to manually turn override:
• Relays
• All Relays ON/OFF
• Groups
• Schedules
• Inputs
• Outputs
• Presets
• Dimmers
From the Main Menu select System Tools and select Manual Control. Once in the manual screen choose one of the selections
above to override and press ENTER on the keypad. For ON/OFF devices, select UP arrow on the keypad to turn ON and DOWN
arrow on the keypad to turn OFF the selection. For the Dimmers select the dimming channel and use the UP keypad to dim up
and the DOWN keypad to dim down.
System Status
The System Status function allows for the user to observe the status of the selections below whether they are seen by the
Controller, to be On or Off, the dimmed state of a dimmer and/or the Sunrise/Sunset times based on programming and operation
for trouble shooting and verication of functionality.
• Panels
• Relays
• Groups
• Inputs
• Outputs
• Dimmers
• Dimmer Inputs
• Sunrise/Sunset