Decoder Wiring and Tips
FIELD WIRING
Proper installation and connection of the decoder two-wire
paths is very important.
Use only Hunter IDWIRE or an approved substitute.
Use only Hunter DBRY-6 waterproof connectors in the red
and blue two-wire path connections.
Leave adequate slack (about 5' or 1.5 m) at each splice, to
prevent disconnection.
Each A2C-D75 output module supports up to 75 decoder
stations.
Each module allows up to three two-wire path connections.
Each path may be up to 10,000' (3 km) with 14 AWG
(2 mm
2
) wire, or up to 15,000' (4.5 km) with 12 AWG
(approximately 3.31 mm
2
) wire.
Two-wire paths may be tee-spliced (in a valve box with
approved connectors), as long as the maximum distance to
each end of the paths from the controller does not exceed
the maximum for the wire used.
You can have more than 75 stations on a single two-wire path.
If more than one A2C-D75 is installed, it is possible to assign
the additional station numbers to another decoder output
module. This must be done with the Station Assignments
function on the Decoder menu, so the controller will know
which module has the additional stations.