46 hunter.direct/ACC2help
Flow Operations
ALARM CLEAR DELAY CONTINUED
This species how long the MainSafe zone will remain shut
down aer a Max Flow or Unscheduled Flow alarm occurs, in
hours:minutes. This is set to 23 hours, 59 minutes, but this can
be changed to other intervals, or set to Manual Only.
If Alarm Clear Delay is set to Manual Only, the
controller will not water again until someone visits
the site, and manually clears the ow alarm. This
assumes a mainline break has occurred and that no
watering should occur until it is repaired.
ALLOWANCES SCREEN
MONTHLY BUDGET
Enter the total amount of ow that can be allowed in this
MainSafe™ in the calendar month. If the total ow exceeds
the monthly budget, an alarm message will appear on the
screen. The controller will not automatically stop watering
when this alarm occurs.
MANUAL WATERING ALLOWANCE
This is an additional amount of ow that is permitted over
all other ow rate limits for manual watering that may occur
during automatic irrigation. An alarm will not occur until other
limits, plus the amount entered here, have been exceeded.