Flow Operations
VIEW FLOW
Current ow rate on all sensors can be viewed from the
Home/Activity screen at any time (or via mobile device, if the
optional Wi-Fi module is installed). Press the so key for View
Flow to see actual ow on up to six ow sensors.
If the controller is equipped with the optional Wi-Fi module,
the current ow can also be viewed on a mobile device.
FLOW ALARM HANDLING
When stations are running, the Flow Monitor continuously
checks the actual ow from the sensor(s) against the
combined learned ow of the stations, including the overow
and underow percentages allowed in the Flow Zone. It also
checks this ow against the higher level Flow Zone limits, and
MainSafe limits if applicable.
If the total amount caused by running stations is exceeded
beyond the permissible station delay periods, the controller
pauses all stations (shutting o the P/MV) in the Flow Zone. It
waits 60 seconds aer the stations are paused, for the ow to
drop to near zero.