Switching point Hysteresis Increment*
ETS 320
°C -25 .. 100 -22 .. 100 1 .. 123 1
°F -13 .. 212 -10 .. 212 1 .. 223 1
ETS 380
°C -30 .. 150 -27 .. 150 1 .. 178 1
°F -22 .. 302 -16 .. 302 2 .. 320 2
Window function
Senso
Lower switch value Upper switch
value
Increment*
ETS 320
°C -25 .. 100 -23 .. 99 -22 .. 100 1
°F -13 .. 212 -11 .. 211 -10 .. 212 1
ETS 380
°C -30 .. 150 -28 .. 149 -27 .. 150 1
°F -22 .. 302 -18 .. 300 -16 .. 302 2
* All ranges given in the table are adjustable by the increments shown.
8 Basic settings
In order to adapt the unit to a particular application, the function of the ETS 300 can be altered via
several basic settings. These are combined in one menu.
8.1 ALTERING THE BASIC SETTINGS
NOTE:
• When the menu is activated no switching operations are carried out.
• Switch off supply voltage or disconnect the unit from the supply voltage.
To close the basic setting menu:
Call up the menu point "END", set to "YES", the ETS 300 returns to the normal display mode after
2 seconds.
NOTE:
• If after about 50 seconds no keys have been pressed, the menu automatically closes
down. Any changes which may have been made will not be saved.
(for summary see 8.2)