12 ETS 300
Status: 29.01.2014 HYDAC ELECTRONIC GMBH Part No.: 669651 E
10 Error messages
If an error is detected, then a corresponding error message appears which must be acknowledged
by pressing any key. Possible error messages are as follows:
E.01 The switching points and hystereses have been set in such a way that the resulting
switch-back point is no longer within the permissible setting range.
Example:
Switching point is set to 65 °C, the hysteresis to 100 °C.
The setting is not correct since the resulting switch-back point is no longer within the
measuring range: the error message is displayed.
Action: Correct the settings
E.10 A data error has been detected in the saved settings. Possible causes are strong
electromagnetic interference or a component fault.
Action: Check all the settings (programming enable, switching points, switch-back points and
basic settings) and correct these if necessary. If the errors occur frequently, please
contact Hydac Service.
E.12 An error has been detected in the stored calibration data. Possible causes are strong
electromagnetic interference or a component fault.
Action: Disconnect the unit and re-connect. If the error message is still displayed, the unit
must be returned to the manufacturer for re-calibration or repair.