32
INsTaLLaTION
Ideal Logic Code Combi ES - Installation and Servicing
WaTER CIRCULaTION sysTEM
1. 


2. 


3. With the system still hot, turn off the gas, water and
electricity supplies to the boiler and drain down to complete

Note: A ushing solution should be used during the ushing
procedure. Flushing solutions: Fernox Superoc,
Sentinel X300 (new systems) or X400 (existing
systems). Refer to Frame 5.
4. 

5. Reset the system initial pressure to the design

6. 
7. Check the condensate drain for leaks and check that it is

8. 
Note: The pump will operate briey as a self-check once every
24 hours in the absence of any system demand.
WaTER TEMpERaTUREs


33
gENERaL ChECKs
DOMEsTIC hOT WaTER (DhW) MODE
1. 



then:

2. Close all taps except the furthest one from the boiler and check

         
approximately 35
o
   

3. 
check that the boiler modulates to deliver DHW at approximately

o

4. 
         
sequence should read:
When the pump stops the display sequence should read:
Note. On systems in excess of 2 bar inlet pressure a water
pressure governor may be required to prevent water noise.
CENTRaL hEa TINg (Ch)
& DOMEsTIC hOT Wa TER (DhW) MODE.
1. 

2. 

3. gas Rate
Check the boiler gas rate when the boiler is at full DHW



4. 

5. 
should go off and the pump continue to run for two minutes

6. 


Make the following checks for correct operation in:
Knob setting Ch Flow Temp
o
C
(
o
F)
DhW Outlet Temp
o
C (
o
F)
Max  
Min 45 (113) 40 (104)
INsTaLLa TION