FaULT FINDINg
FaULT FINDINg F aULT FINDINg F aULT FINDINg F aULT FINDINg F aULT FINDINg
Ideal Logic Code Combi ES - Installation and Servicing
80
aLTERNa TINg ‘F’ aND ‘5’ - RETURN ThERMIsTOR FaULT


Check the resistance using a suitable multimeter

At 25
o
     

o
     

o
C expect 1,000 - 1,100 Ohms




NO
81
aLTERNa TINg ‘F’ aND ‘6’ - OUTsIDE sENsOR F aULT

Check the resistance using a suitable multimeter

At 0
o
C expect 31,000 - 35,000 Ohms
At 15
o
     
At 30
o
     


Is the wiring securely connected between the
incoming terminal block boiler connection of the




NO


Is the wiring securely connected at both the boiler and



NO


NO


Check and replace wiring as necessary
NO
