FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722 13-7
13: T
ROUBLESHOOTING
36
DLOG/TRACE is executed but the capacity of CSV file exceeds the maximum size of a day or the number of files
exceeds the maximum number of a day.
41 SD memory card is write protected.
42
The result of execution using the SCRPT instruction is a value that indicates anything other than normal
completion.
46
In the SCALE instruction, the input minimum value is larger than the input maximum value, the output minimum
value is larger than the output maximum value, or the dead band data exceeds the valid range.
48 Pulse output instructions using the same pulse output are executed at the same time.
49
Pulse output instructions referring to the absolute position counter are executed without initializing the absolute
position counter with ABS instruction.
User Program
Execution Error Code
(D8006)
Error Details